Turbovex - Headquarter f or Ventilation

TX 700

TX 700 is the model to consider if you need a floor model of decentralized ventilation systems

With an output of up to 700 m3/h, TX 700 is suitable for ventilation in conference and meeting rooms, auditoriums and the like. Depending on the level of activity in the rooms and their size, several systems can be juxtaposed and operated either cooperatively or independently


Multiple installation options.TX 700 can be placed along the wall or in a corner.

Designed for draft-free supply of fresh air at floor level(the air is distributed in accordance with the displacement principle), Air is blown in at ground leved and and extracted at a height of approx. 2 m.

Standard equipment: (Replaceable filters, internal automatic dampers, heat exchangers with heat recovery, automatic bypass, low energy motors with an energy consumption of 1.1 Kj/m³, reheater for connection to electricity (connection for district heating/central heating on request) and electronic control unit.

Demand controlled ventilation. Systems can be ordered with PIR,( Passive Infra Red Sensor) CO2 sensor and hygrometer as optional equipment.

Standard color is RAL 9010. Also available in other RAL colors at extra charge.


Technical specifications

 

Dimension H x B x D

2000 x 700 x 510 mm

Air circulation:

300-680 m³/h

Temperature efficiency:

65 %

Filter:

F5

Weight:

95 kg

Power connection:

1 x 230 V/50Hz

Power (engine):

200 Watts

Energy consumption:

1.05 kJ/m³

Electric reheater:

2670 Watts

Sound level:

26-36 dbA

Duct connection:

2 x Ø 315

 

 

 

Control for TX 700: